Description
The FieldPoint module FP-AO-210, part number 18579.2 (777518-210), is designed for analog voltage output applications. This module is categorized under FieldPoint and is identified by its model number FP-AO-210. It is important to note that this module is not recommended for new designs.
The FP-AO-210 features 8 output channels, which are single-ended. These channels have a Digital-to-Analog Converter (DAC) resolution of 12 bits, allowing for precise control over the output signals. The output range of this module is between 0 V and 10 V, with an output resolution of 2.5 mA. Upon power up, the default output is set to 0 V, ensuring a safe start-up condition.
For protection, the module is equipped with overvoltage protection that ranges from -10 to 20 V, and it can tolerate transient voltages up to 2300 Vrms. Additionally, the module offers an isolation of 250 Vrms, further enhancing its safety and reliability in various applications.
The update rate of the FP-AO-210 can reach up to 200 updates/sec, making it suitable for applications requiring fast response times. It also features 2 green LED indicators (for POWER and READY) and 1 red LED (for Overcurrent), providing visual feedback on the module’s status and any issues.
Each channel of the FP-AO-210 has an internal power source that can supply up to 1 mA. Additionally, an external power supply rated at 15 is required for its operation, ensuring that the module is powered adequately for optimal performance.
| Specification | Details |
|---|---|
| Part Number | 18579.2 (777518-210) |
| Category | FieldPoint |
| Model | FP-AO-210 |
| Description | 8 ch Analog Voltage Output Module (Not for New Design) |
| Channels | 8 output channels, single-ended |
| DAC Resolution | 12 bits |
| Output Range | 0 V – 10 V |
| Output Resolution | 2.5 mA |
| Default Output on Power Up | 0 V |
| Overvoltage Protection | -10 – 20 V |
| Transient Voltage Tolerance | 2300 Vrms |
| Isolation | 250 Vrms |
| Update Rate | Up to 200 updates/sec |
| LED Indicators | 2 Green (POWER and READY), 1 Red (Overcurrent) |
| Internal Power Source per Channel | Up to 1 mA |
| External Power Supply | 15