Description
The FieldPoint FP-DO-403 is designated by the part number 186085A-01 (777518-403) and falls within the category of FieldPoint systems. This model is a 16-channel discrete output module that specializes in sinking operations. Each of these channels is capable of sinking digital output, ensuring versatile application across various systems.
The module is equipped with On/Off LED indicators for easy status monitoring, ensuring users can quickly ascertain the operational state of each channel. For installation, it is designed to mount onto an FP-TB-x FieldPoint Terminal Base, facilitating a seamless integration into existing setups.
Powering this module requires 600 mW from the network module, which is a testament to its efficiency in operation. The output impedance is remarkably low at 0.12 Ω, ensuring minimal resistance in the circuit. Furthermore, it boasts a quick delay time of 50 μs, allowing for rapid signal processing.
In terms of performance, the OFF State Leakage is kept minimal at 50 μA, preventing unnecessary power dissipation. The module’s output capacity is robust, capable of handling 2 A per channel or 16 A squared per module, making it suitable for high-demand applications. It is also designed to be compatible with a voltage range of 5 to 30 VDC, offering flexibility in terms of power requirements.
The FP-DO-403 ensures safety and reliability with an isolation rating of 250 Vrms CAT II channel-to-ground, protecting against potential electrical hazards. Additionally, it has been subjected to a dielectric withstand test, successfully enduring 2,300 Vrms for 5 seconds, further demonstrating its durability and safety in challenging environments.
| Specification | Details |
|---|---|
| Part Number | 186085A-01 (777518-403) |
| Category | FieldPoint |
| Model | FP-DO-403 |
| Description | 16Ch Discrete Output Module, Sinking |
| Channels | 16 sinking digital output |
| Indicators | On/Off LED |
| Mounting | FP-TB-x FieldPoint Terminal Base |
| Power Requirement | 600 mW from the network module |
| Output Impedance | 0.12 Ω |
| Delay Time | 50 μs |
| OFF State Leakage | 50 μA |
| Output Capacity | 2 A per channel or 16 A squared per module |
| Voltage Compatibility | 5 to 30 VDC |
| Isolation | 250 Vrms CAT II channel-to-ground |
| Dielectric Withstand Test | 2,300 Vrms, 5 s |
| Weight |