Description
The FieldPoint module with the part number 777318-124 is known as the FP-RTD-124. This module is specifically designed for 4 Wire RTD Input with a 16 Bit resolution, although it is recommended not for new design. It supports 8 inputs for 2-wire and 4-wire RTDs, making it versatile for various temperature sensing tasks.
Each input channel of the FP-RTD-124 features positive sensing input, negative sensing input, excitation output, and common input terminals. This module is capable of linearizing temperatures for 100 Ω or 1000 Ω platinum RTDs, across six Temperature Coefficient of Resistance (TCR) values, offering precise measurements across diverse applications.
When it comes to temperature range, this module can measure temperatures from –200 to 850 °C, equivalent to 73 to 1,123 K or –328 to 1,562 °F, with an impressive resolution of 0.016 °C. It updates temperature readings at a rate of 1 update/second per channel, ensuring timely data for critical applications.
The FP-RTD-124 is also designed with efficiency in mind, consuming only 35 mW of power. Users have the flexibility to scale data in terms of Resistance (Ω) or temperature units (°C, °F, °K), according to their specific needs. Notable features of this module include its ability to be hot-swapped, auto-configuration capabilities, built-in signal conditioning, and 50/60 Hz noise rejection filters, enhancing its functionality and reliability in various industrial settings.
| Specification | Detail |
|---|---|
| Part Number | 777318-124 |
| Category | FieldPoint |
| Model | FP-RTD-124 |
| Description | 4 Wire RTD Input Module, 16 Bit (Not for New Design) |
| Input Channels | 8 inputs for 2-wire and 4-wire RTDs |
| Input Channel Terminals | Positive sensing input, negative sensing input, excitation output, common input |
| Linearization | 100 Ω or 1000 Ω platinum RTDs, 6 TCR values |
| Temperature Ranges | –200 to 850 °C, 73 to 1,123 K, –328 to 1,562 °F |
| Resolution | 0.016 °C |
| Update Rate | 1 update/second per channel |
| Power Consumption | 35 mW |
| Data Scaling Options | Resistance (Ω) or temperature units (°C, °F, °K) |
| Features | Hot-swappable, auto configuration, built-in signal conditioning, 50/60 Hz noise rejection filters |
Question 1: What is the part number for the FP-RTD-124?
Answer 1: 777318-124
Question 2: How many inputs does the FP-RTD-124 support?
Answer 2: 8 inputs for 2-wire and 4-wire RTDs
Question 3: What temperature range can the FP-RTD-124 measure?
Answer 3: –200 to 850 °C or –328 to 1,562 °F
Question 4: What is the power consumption of the FP-RTD-124?
Answer 4: 35 mW
Question 5: Does the FP-RTD-124 offer hot-swappable functionality?
Answer 5: Yes