Description
The product described by part number 187208J-01, also known as 777318-124, falls under the FieldPoint category. It is identified by the model FP-RTD-124 and is a 4 Wire RTD Input Module with a 16 Bit resolution. However, it is important to note that this module is not recommended for new designs.
This module is capable of accommodating 8 inputs for both 2-wire and 4-wire RTDs. Each of these input channels includes 4 terminals: a positive sensing input, a negative sensing input, an excitation output, and a common input. The module supports 100 Ω or 1000 Ω nominal resistance platinum RTDs and provides compatibility with 6 TCR values.
Regarding its performance in different environments, the module boasts an impressive temperature range from -200 to 850 °C (73 to 1,123 K, -328 to 1,562 °F), with a resolution of 0.016 °C. It updates data at a rate of 1 update/second per channel, ensuring timely and accurate readings.
The module’s power consumption is minimal, requiring only 35 mW from a network module. Users have the option to scale data in resistance (Ω) or in various temperature units (°C, °F, °K), providing flexibility in data representation.
Among its key features, the module is hot-swappable and supports auto configuration. It also includes built-in signal conditioning with 50/60 Hz noise rejection filters, enhancing the quality and reliability of the data captured.
| Specification | Detail |
|---|---|
| Part Number | 187208J-01 (Also known as 777318-124) |
| Category | FieldPoint |
| Model | FP-RTD-124 |
| Description | 4 Wire RTD Input Module, 16 Bit (Not for New Design) |
| Input Channels | 8 inputs for 2-wire and 4-wire RTDs |
| Terminals per Channel | 4 (positive sensing input, negative sensing input, excitation output, common input) |
| Supported RTDs | 100 Ω or 1000 Ω nominal resistance platinum RTDs and 6 TCR values |
| Temperature Range | -200 to 850 °C, 73 to 1,123 K, -328 to 1,562 °F |
| Resolution | 0.016 °C |
| Update Rate | 1 update/second per channel |
| Power Consumption | 35 mW from a network module |
| Data Scaling Options | Resistance (Ω) or temperature units (°C, °F, °K) |
| Features | Hot-swappable, auto configuration, built-in signal conditioning with 50/60 Hz noise rejection filters |