Description
The product with the part number 184506A-01, also known under the alternate part number 777519-02, falls within the FieldPoint category. It is designated as model FP-TB-2. This model features 36 spring terminals designed to accommodate a wire size ranging from 16–26 AWG copper conductor. For optimal connection, the insulation stripping requirement is specified as 0.28 in..
In addition to the main terminals, there are 4 dedicated terminals (comprising two V and two C terminals) and 32 numbered terminals to facilitate organized wiring and connections. It is compatible with all I/O modules, with the exception of dual-channel modules, offering a wide range of application possibilities.
For installation, the FP-TB-2 can be mounted on DIN-rails or panels, providing flexibility in setup according to the requirements of the specific application. Each terminal is capable of handling a current capacity of up to 10 A, with a maximum return path current of <3 A and a maximum channel-to-earth voltage of 250 V.
This model is designed to operate within a temperature range of -40° C to 70° C, ensuring reliability and performance even in extreme conditions. It is classified under pollution degree 2, indicating that it is designed to operate in environments where only non-conductive pollution occurs.
| Specification | Detail |
|---|---|
| Part Number | 184506A-01 |
| Alternate Part Number | 777519-02 |
| Category | FieldPoint |
| Model | FP-TB-2 |
| Terminals | 36 spring terminals |
| Wire Size | 16–26 AWG copper conductor |
| Insulation Stripping | 0.28 in. |
| Dedicated Terminals | 4 (two V and two C terminals) |
| Numbered Terminals | 32 |
| Compatible I/O Modules | All except dual-channel modules |
| Mounting | DIN-rails or panels |
| Current Capacity (per terminal) | 10 A |
| Maximum Return Path Current | <3 A |
| Maximum Channel-to-Earth Voltage | 250 V |
| Operating Temperature | -40° C to 70° C |
| Pollution Degree | 2 |
Question 1: What is the part number for FP-TB-2?
Answer 1: 184506A-01 or 777519-02
Question 2: How many spring terminals does FP-TB-2 have?
Answer 2: 36 spring terminals
Question 3: What wire size does FP-TB-2 support?
Answer 3: 16–26 AWG copper wires
Question 4: Can FP-TB-2 be used with dual-channel I/O modules?
Answer 4: No, it’s incompatible with dual-channel modules.
Question 5: What is FP-TB-2’s max channel-to-earth voltage?
Answer 5: 250 V