Description
The National Instruments FP-AIO-600 Analog Input/Output Module, bearing the part number 189830H-01 (777518-600), falls under the FieldPoint category. This module is designed to facilitate both input and output operations related to analog signals.
It features 4 analog input channels that can handle either current or voltage signals, making it versatile for various applications. Additionally, it is equipped with 4 analog output channels, which are specifically designed for current signals. This balance between input and output capabilities ensures that the module can be effectively employed in a wide range of automation tasks.
The hardware update rate of the module is 1.7 kHz, which allows for high-speed data processing and signal handling. This is complemented by a 12-bit resolution, ensuring that the data is both accurate and precise.
From a protection standpoint, the module is well-equipped to handle input signals up to ±10 V or ±100 mA, thereby guarding against potential damage from overvoltage or overcurrent situations. The input ranges for current sources are quite flexible, offering +20 to -20 mA, 0 to 20 mA, and 4 to 20 mA options to accommodate different types of sensors and signals.
The module’s output current source requires an externally located 10 VDC to 30 VDC 125 mA power supply, which provides the necessary power for the output operations. Isolation is another key feature of the FP-AIO-600, with output channels and their common terminals isolated from other I/O modules. However, it is important to note that there is no isolation between the input and output channels within the module itself.
The default output range is set to 0 to 20 mA, which suits a wide variety of applications. Additionally, the module includes a monitoring circuit with open-loop detection, enhancing its safety and reliability during operation. Lastly, the presence of a status indicator
| Specification | Detail |
|---|---|
| Part Number | 189830H-01 (777518-600) |
| Category | FieldPoint |
| Model | FP-AIO-600 |
| Description | National Instruments FP-AIO-600 Analog Input/Output Module |
| Analog Input Channels | 4 (current or voltage) |
| Analog Output Channels | 4 (current) |
| Hardware Update Rate | 1.7 kHz |
| Resolution | 12-bit |
| Input Protection | ±10 V or ±100 mA |
| Input Ranges for Current Sources | +20 to -20 mA, 0 to 20 mA, 4 to 20 mA |
| Output Current Source | Externally located 10 VDC to 30 VDC 125 mA power supply |
| Isolation | Output channels and their common terminals isolated from other I/O modules; No isolation between input and output channels |
| Default Output Range | 0 to 20 mA |
| Monitoring Circuit | Yes, with open-loop detection |
| Status Indicator |