Description
The FP-1000 RS232/RS485 Network Module, bearing the part number 184120F-01 (777517-00), falls under the FieldPoint category. This module is designed for specific applications and is noted as “Not for New Design,” indicating that it may be nearing the end of its production or support life.
The FP-1000 model utilizes an RS232/RS485 interface, capable of supporting a maximum of 25 network modules. Additionally, it can accommodate up to 225 I/O modules on an RS-485 network, showcasing its capacity for extensive network configurations. The module offers a range of switch selectable baud rates, including 300, 1200, 2400, 9600, 38400, 57600, and 115200, allowing for versatile communication speeds.
For RS-232 connections, it supports a maximum cabling separation of 50 ft, with potential for extensions, providing flexibility in network layout and device placement. The power consumption of the FP-1000 is minimal, at 1 watt, plus the additional power required by connected I/O modules, calculated as 1.15 times the sum of I/O Module Consumption. It operates within a power supply range of 11 to 30 VDC, accommodating various power sources.
Included with the FP-1000 is a comprehensive suite of software tools, such as FieldPoint Explorer, BridgeVIEW server, Lookout driver class, LabVIEW Vis, LabWindows/CVI functions, and an OPC server. These tools provide extensive capabilities for system setup, monitoring, and control.
The module’s physical weight is 8.7 oz, making it relatively lightweight and easy to install in a variety of settings. It is designed to operate within a wide temperature range of -40°C to +70°C, ensuring reliable performance in extreme environmental conditions.
| Specification | Detail |
|---|---|
| Part Number | 184120F-01 (777517-00) |
| Category | FieldPoint |
| Model | FP-1000 |
| Description | FP-1000 RS232/RS485 Network Module (Not for New Design) |
| Interface | RS232/RS485 |
| Maximum Network Modules | 25 |
| Maximum I/O Modules | 225 on RS-485 network |
| Baud Rates (Switch Selectable) | 300, 1200, 2400, 9600, 38400, 57600, 115200 |
| Maximum RS-232 Cabling Separation | 50 ft (with potential for extensions) |
| Power Consumption | 1 watt + 1.15 * Σ(I/O Module Consumption) |
| Power Supply Range | 11 to 30 VDC |
| Software Included | FieldPoint Explorer, BridgeVIEW server, Lookout driver class, LabVIEW Vis, LabWindows/CVI functions, OPC server |
| Weight | 8.7 oz |
| Operating Temperature Range | -40°C to +70°C |