184437C-01

The FP-DI-301, part number 184437C-01, is a 16-channel, 24 VDC sinking input module with a 1 kHz update rate, designed for robust performance across various conditions.

In Stock | Ships Today

img

    Description

    The FP-DI-301, with a part number of 184437C-01, is a highly sophisticated digital input module designed to accommodate a wide range of industrial applications. This module features 16 input channels, each capable of handling a 24 VDC sinking input type. It is engineered to provide a high update rate of 1 kHz for all channels, ensuring timely and accurate data processing.

    For versatility in various working conditions, the FP-DI-301 supports an input range of 18 to 30 VDC, with reverse voltage protection up to -30 VDC, safeguarding the module against potential damage from incorrect power supply connections. The input impedance is rated at 5 kΩ, optimizing the module for a broad spectrum of signal sources.

    Despite its robust performance capabilities, the FP-DI-301 remains energy efficient with a power consumption of just 400 mW. Additionally, it is built to operate reliably in extreme temperatures, with an operating temperature range of -40 to 70 °C and a storage temperature range of -55 to 85 °C. This module can also withstand relative humidity levels from 10 to 90%, non-condensing, ensuring its resilience in varying environmental conditions.

    To further its reliability, the FP-DI-301 is designed to endure significant vibration levels during operation, withstanding both random vibration of 5 grms and sinusoidal vibration of 5 g across a frequency range of 10 to 500 Hz. Weighing in at 4.93 oz, it remains a lightweight yet sturdy component for any system.

    Adhering to stringent safety standards, the FP-DI-301 complies with multiple electrical safety regulations, including IEC 61010-1, EN-61010-1, UL 61010-1, and CSA 61010-1, ensuring its suitability for global deployment in a wide array of industrial settings.

    Question 1: What’s the update rate of FP-DI-301?
    Answer 1: 1 kHz for all channels.

    Question 2: How many input channels does FP-DI-301 have?
    Answer 2: 16 channels, 24 VDC sinking input.

    Question 3: What is the power consumption of FP-DI-301?
    Answer 3: 400 mW, making it energy efficient.

    Question 4: What safety standards does FP-DI-301 meet?
    Answer 4: IEC 61010-1, EN-61010-1, UL 61010-1, and CSA 61010-1.

    Question 5: Can FP-DI-301 operate in extreme temperatures?
    Answer 5: Yes, from -40 to 70 °C.

    Specification Detail
    Part Number 184437C-01
    Model FP-DI-301
    Input Channels 16
    Input Type 24 VDC sinking
    Update Rate 1 kHz for all channels
    Input Range 18 to 30 VDC
    Reverse Voltage Protection -30 VDC
    Input Impedance 5 kΩ
    Power Consumption 400 mW
    Operating Temperature Range -40 to 70 °C
    Storage Temperature Range -55 to 85 °C
    Relative Humidity 10 to 90%, non-condensing
    Vibration (Operating) Random: 5 grms; Sinusoidal: 5 g (10 to 500 Hz)
    Weight 4.93 oz
    Electrical Safety Standards IEC 61010-1, EN-61010-1, UL 61010-1, CSA 61010-1