img

186434A-01

The 186434A-01 (FP-RLY-422) is a 4-channel FieldPoint relay module with a max 3 A switching capacity, designed for electromechanical operations.

In Stock | Ships Today

img

    Description

    The FP-RLY-422 is a 4 Channel Relay Module designed for FieldPoint systems, identified by its part number 186434A-01 (also known as 777518-422). This module is not recommended for new designs but remains a viable option for existing systems. It features a maximum switching capacity of 3 A at 250 VAC or 35 VDC and consumes approximately 1.5 W of power.

    The relay type employed is an Electromechanical Form C, Break-Before-Make, ensuring reliable operation. With dimensions of 10.7 x 10.9 x 9.1 cm and a weight of 180 g, it’s compact and easy to integrate into various setups. The module’s expected relay life is impressive, with up to 1 x 107 operations/s mechanically and 300,000 operations at 35 VDC, 3 A electrically. It boasts a quick operate time of 1 ms, a release time of 5 ms, and a bounce time of 3 ms, ensuring swift and reliable switching.

    Additionally, the FP-RLY-422 features integrated module-to-module isolation, enhancing the system’s overall safety and reliability. This technical specification underscores the module’s efficiency and durability in various applications.

    Specification Details
    Part Number 186434A-01 (Also known as 777518-422)
    Category FieldPoint
    Model FP-RLY-422
    Description 4 Channel Relay Module (Not for New Design)
    Channels 4
    Maximum Switching Capacity 3 A at 250 VAC or 35 VDC
    Power Consumption 1.5 W
    Relay Type Electromechanical Form C, Break-Before-Make
    Dimensions 10.7 x 10.9 x 9.1 cm
    Weight 180 g
    Expected Relay Life (Mechanical) 1 x 107 operations/s
    Expected Relay Life (Electrical) 300,000 operations at 35 VDC, 3 A
    Operate Time 1 ms
    Release Time 5 ms
    Bounce Time 3 ms
    Isolation Integrated module-to-module

    Question 1: What is the max switching capacity of FP-RLY-422?
    Answer 1: 3 A at 250 VAC or 35 VDC

    Question 2: How much power does the FP-RLY-422 consume?
    Answer 2: Approximately 1.5 W

    Question 3: What is the relay type used in FP-RLY-422?
    Answer 3: Electromechanical Form C, Break-Before-Make

    Question 4: What is the mechanical relay life of FP-RLY-422?
    Answer 4: Up to 1 x 10^7 operations/s

    Question 5: Does FP-RLY-422 have module-to-module isolation?
    Answer 5: Yes