Description
The product with the part number 19099.3 and an alternate part number of 777518-550 falls under the category of FieldPoint. It is specifically the model FP-DIO-550, which is a Digital Input/Output Module. It is important to note that this module is not recommended for new designs. This module features a channel configuration that includes 8 Input / 8 Output Digital Channels.
When it comes to compatibility, the input channels of this module can work with sourcing, sinking, and differential devices. The output channels type is designed for sourcing digital output. Additionally, the module boasts current limiting capabilities up to 7 mA and offers short circuit protection under operating temperatures ranging from -40°C to 70°C.
Regarding safety and durability, it has passed a Dielectric Withstand Test, sustaining 5 seconds at 250 Vrms CAT-II. It also provides channel to ground isolation at 2,300 Vrms, ensuring the safety and reliability of the module in various operating conditions. The module’s operating power source is a FieldPoint Terminal Base (FP-TB-x).
The input voltage ranges are specifically designed to identify the state of the module accurately. For an OFF state, the input voltage should be below 5 V. An uncertain state is determined by an input voltage range of 5 V to 11 V, while an ON state requires an input voltage range of 11 V to 30 V. Lastly, for system safety, it is recommended to connect the module’s system safety ground to the Protective Earth Ground Terminal on the FieldPoint Backplane (FP-BPx).
| Specification | Detail |
|---|---|
| Part Number | 19099.3 |
| Alternate Part Number | 777518-550 |
| Category | FieldPoint |
| Model | FP-DIO-550 |
| Description | Digital Input/Output Module (Not for New Design) |
| Channel Configuration | 8 Input / 8 Output Digital Channels |
| Input Channels Compatibility | Sourcing, Sinking, Differential Devices |
| Output Channels Type | Sourcing Digital Output |
| Current Limiting | Yes, up to 7 mA |
| Short Circuit Protection | Yes, under -40°C to 70°C operating temperature |
| Dielectric Withstand Test | 5 s at 250 Vrms CAT-II |
| Channel to Ground Isolation | 2,300 Vrms |
| Operating Power Source | FieldPoint Terminal Base (FP-TB-x) |
| Input Voltage Range for OFF State | Below 5 V |
| Input Voltage Range for Uncertain State | 5 V to 11 V |
| Input Voltage Range for ON State | 11 V to 30 V |
| System Safety Ground | Connect to Protective Earth Ground Terminal on FieldPoint Backplane (FP-BPx) |
Question 1: What are the alternate part numbers for FP-DIO-550?
Answer 1: 19099.3 and 777518-550
Question 2: What is the channel configuration of FP-DIO-550?
Answer 2: 8 Input / 8 Output Digital Channels
Question 3: What current limiting does FP-DIO-550 offer?
Answer 3: Up to 7 mA
Question 4: What is the isolation voltage for FP-DIO-550?
Answer 4: 2,300 Vrms
Question 5: What input voltage indicates an ON state for FP-DIO-550?
Answer 5: 11 V to 30 V