Description
The NI cFP-CB-4 Compact FieldPoint Probeable Connector Block, with the part number 780017-04, features a removable connector that includes 20 screw terminals for efficient wiring and signal connection.
This connector block is designed for mounting on the cFP-BP-x or cFP-180x Compact FieldPoint Backplane, making it ideal for various applications such as linking sensors and actuators, prototyping, and troubleshooting.
For environments with hazardous voltage or high vibration, it is highly recommended to use wire ferrules on signal wires to ensure safety and reliability. The connector block incorporates V terminals for VSUP and C terminals for COM, each set being internally connected to provide a streamlined wiring process.
When attaching wires, a flathead screwdriver with a blade size of less than 0.09 x 0.04 inches is needed, and users should strip approximately 0.35 inches of insulation from the wire ends. The screw terminals should be securely fastened with a torque of 0.22–0.25 N · m (1.9–2.2 lb · in.) to ensure a proper connection.
The cFP-CB-4 includes 4 built-in CJC (Cold Junction Compensation) sensors to maintain accuracy in temperature measurements, with a typical cold-junction accuracy of 0.15 °C and a maximum of 0.3 °C. Weighing 5.0 oz, this connector block is built to withstand operating temperature ranges from -40°C to 70°C and is suitable for various industrial environments.
Specification | Detail |
---|---|
Part Number | 780017-04 |
Product Name | NI cFP-CB-4 Compact FieldPoint Probeable Connector Block |
Removable Connector | 20 screw terminals |
Mounting | cFP-BP-x or cFP-180x Compact FieldPoint Backplane |
Use Case | Linking sensors and actuators, prototyping, troubleshooting |
Wire Ferrules | Recommended for hazardous voltage and/or high vibration |
Terminals | V terminals for VSUP; C terminals for COM (internally linked respectively) |
Screwdriver Size for Terminals | Less than 0.09 x 0.04 inches flathead |
Wire Insulation Stripping | 0.35 inches |
Screw Terminal Torque | 0.22–0.25 N · m (1.9–2.2 lb · in.) |
Built-in CJC | 4 |
Cold-Junction Accuracy | 0.15 °C typical, 0.3 °C maximum |
Weight | 5.0 oz |
Operating Temperature Range | –40 |
Question 1: How should wire ferrules be used with the NI cFP-CB-4 Compact FieldPoint Probeable Connector Block to enhance safety and reliability in high vibration or hazardous voltage environments?
Answer 1: Wire ferrules should be used on signal wires connected to the NI cFP-CB-4 Compact FieldPoint Probeable Connector Block to enhance safety and reliability in environments with high vibration or hazardous voltage by ensuring a secure and stable connection within the screw terminals.
Question 2: What are the specifications for proper wire attachment when using the NI cFP-CB-4 Compact FieldPoint Probeable Connector Block with part number 780017-04?
Answer 2: The torque specification for securely fastening the screw terminals on the NI cFP-CB-4 Compact FieldPoint Probeable Connector Block to ensure a proper connection is 0.22–0.25 N · m (1.9–2.2 lb · in.).
Question 3: What are the specific requirements for attaching wires to the NI cFP-CB-4 Compact FieldPoint Probeable Connector Block, including the necessary tools and the torque needed to ensure a proper connection?
Answer 3: A flathead screwdriver with a blade size of less than 0.09 x 0.04 inches should be used for attaching wires to the NI cFP-CB-4 Compact FieldPoint Probeable Connector Block, and the screw terminals should be securely fastened with a recommended torque of 0.22–0.25 N · m (1.9–2.2 lb · in.).
Question 4: What is the torque specification for securely fastening the screw terminals on the NI cFP-CB-4 Compact FieldPoint Probeable Connector Block to ensure a proper connection?
Answer 4: To attach wires to the NI cFP-CB-4 Compact FieldPoint Probeable Connector Block, one needs a flathead screwdriver with a blade size of less than 0.09 x 0.04 inches to tighten the screw terminals after stripping approximately 0.35 inches of insulation from the wire ends, and the terminals should be fastened with a torque of 0.22–0.25 N · m (1.9–2.2 lb · in.) to ensure
Question 5: What blade size should be used for attaching wires to the NI cFP-CB-4 Compact FieldPoint Probeable Connector Block, and what is the recommended torque for securing the screw terminals?
Answer 5: When attaching wires to the NI cFP-CB-4 Compact FieldPoint Probeable Connector Block with part number 780017-04, use a flathead screwdriver with a blade size of less than 0.09 x 0.04 inches to secure the wires, which should have approximately 0.35 inches of insulation stripped from the ends, and tighten the screw terminals to a torque of 0.22–0.25 N·m (1.9–2.2